To solve this problem, a method of valve power loss estimation based on the detailed equivalent simulation model of MMC is proposed. Results of valve power loss analysis of 201-level 500MW MMC operating at 50Hz~1000Hz are presented.
It is seen that the valve power loss of a MMC increased by 12, 40 and 93 % under 200Hz, 500Hz and 1000Hz operating frequency. The article concludes that in a device with isolated inner AC system, MMC operating at higher frequency will be more competitive than typical 50Hz/60Hz MMC with moderate increase of operating power loss and significant reduction of the size of the AC components.
by Gangadhara Swamy | Molugu Shruthi "Power Loss Evaluation Method for Modular Multi-Level Converter with High-Frequency"
Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-2 | Issue-1 , December 2017,
URL: http://www.ijtsrd.com/papers/ijtsrd7027.pdf
Direct URL: http://www.ijtsrd.com/engineering/electrical-engineering/7027/power-loss-evaluation-method-for-modular-multi-level-converter-with-high-frequency/gangadhara-swamy